The air humidity meter is used to measure and store environmental data such as temperature, humidity, illuminance, CO2 content and TVOC concentration. The air humidity meter also calculates the dew point, absolute humidity and the water vapor content in the air. The air humidity meter is used for stationary monitoring of laboratories, greenhouses, medicine and food stores, museums, etc. The data measured and calculated by the air humidity meter are stored in the internal memory and can be called up via Ethernet and sent to the user. In addition to storing the measurement data, the air humidity meter can send alarms by email or display them on a website. The air humidity meter can be supplied via a power supply unit or autonomously via Power over Ethernet. An internal battery is built into the air humidity meter to buffer the memory and the settings.

 

In addition to the built-in Ethernet interface, the air humidity meter also has an RS485 interface available to the user. This can be addressed via Modbus RTU. The user can communicate with the air humidity meter via Modbus TCP / IP, HTTP, FTP via the Ethernet interface. A web and FTP server as well as a DHCP and SMTP client complete the functionality of the air humidity meter's network interface.

 

 

Manual

Air Humidity Meter PCE-HT 422

數量
  • - Temperature measuring range (-20 ... +60 °C)

    - Relative humidity measuring range (0 ... 95%)

    - CO2, TVOC and light measurement

    - Ethernet interface (PoE compatible)

    - Alarm (acoustic, email, visual)

    - 4 GB memory

    - Adjustable sampling / storage rate

    - FTP, HTTP server

  • Measured variable Air humidity
    Measuring range 0 ... 95% r.H. 
    Accuracy  ± 3 % of reading (10 .. 90 %)
      ± 5 % of other
    Resolution  -
       
    Measured variable Temperature
    Measuring range -20 ... 60 °C
    Accuracy  ± 0.6 °C (10 ... 40 °C)
      ± 1 °C of other
    Resolution  -
       
    Measured variable Illuminance
    Measuring range 0 ... 60000 lx
    Accuracy  -
    Resolution  -
       
    Measured variable TVOC
    Measuring range 0 ... 60000 ppb 
    Accuracy  -
    Resolution  1 ppb (0 ... 2008 ppb)
      6 ppb (... 11110 ppb) 
      32 ppb (... 60000 ppb)
       
    Measured variable CO2
    Measuring range 400... 60000 ppm
    Accuracy  -
    Resolution  1 ppm (400 ..1479ppm)
      3 ppm (... 5144 ppm)
      9 ( ...17597 ppm)
      31 ppm ( .. 60000 ppm)
       
    Measured variables dew point absolute humidity
      saturated steam pressure, enthalpy
    Interface  RS485 (Modbus RTU)
    Ethernet Modbus TCP, HTTP, FTP, MQTT
    Memory 4 GB
    Power supply DC power pack 6 V / 1 A
      PoE IEEE 802.3af
    Power consumption < 2 VA
    Warm-up time 15 minutes
    Operating conditions -20 ... 60°/ 95% r.H
    Degree of protection IP20
    Mounting Rear mounting hole for
      Wall mounting, sensor facing down
    Dimensions  120 x 80 x 25 mm
    Weight  300 g