For monitoring: Carbon monoxide, Nitrogen dioxide, Methane, Propane, Hydrogen
Key Features
- 1, 2 or 3 channel operation with internal and/or remote sensor configurations
- Modbus® RS-485 RTU communication
- LCD display
- 24 VDC power
- 4-conductor daisy chain network wiring
- Standard water / dust tight, corrosion resistant enclosure (drip proof)
- IP54 rated with optional splash guard installed.
Description
The LPT-P is an economical, three channel, digital transmitter that is designed to be part of a gas detection system for enclosed parking facilites/parkades and vehicle repair shop applications. It can be configured with a single and/or dual internal electrochemical Carbon monoxide (CO) and/or Nitrogen dioxide (NO2) sensor and/or one catalytic combustible ESH-A Remote Sensor.
The LCD display provides at-a-glance gas readings for each channel along with alarm and communication status. Navigating the menu can be done unobtrusively with a magnetic wand or by using the internal programming buttons.
The LPT-P is not a standalone gas detection device, it operates on a local area network (LAN) using Modbus® RS-485 RTU serial communications with a Controller, a control panel, Direct Digital Control system (DDC) or a Building Automation System (BAS). The LPT-P does not have an internal alarm or relay.
The LPT-P comes in a standard water / dust tight, corrosion resistant ABS/ polycarbonate enclosure with a hinged, secured door. With the optional splash guard installed, the enclosure is IP54 rated and ideal for use in water spray or wash down applications.
LPT-P Digital Car Park Transmitter
Target Gas
Gas Sensors
Carbon monoxide (CO), Nitrogen dioxide (NO2), Hydrogen (H2), Methane (CH4), Propane (C3H8)
Mechanical
Enclosure
ABS / Polycarbonate, corrosion resistant
Copper coated interior to reduce RF interference
IP54 rated with splash guard installed
Weight
363 g / 0.8 lbs
Size
127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches
User Interface
Display
Graphic LCD, white border
Magnetic switches to initiate calibration without opening the enclosure
Input/Output
Output
Modbus® RS-485 RTU
Electrical
Power Requirement
16-30 VDC, 3 W, Class 2
Current Draw
45 mA @24 VDC (max)
Wiring
LAN Modbus® RTU (version 1.1b3) RS-485, 16 gauge, 4-conductor shielded network wiring (daisy-chain)
Fuses
Thermal, resetting
Environmental
Operating Temperature
-20°C to 40°C (-4°F to 104°F)
Operating Humidity
15 - 90% RH non-condensing